Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 214

Advertising
background image

214

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 4

Motor Control

Step 4 – Determine the Minimum Resistance

Each drive with an internal DB IGBT has a minimum resistance associated with
it. If a resistance lower than the minimum value for a given drive is connected, the
brake transistor will likely be damaged. Below is a table of minimum resistances
for frame 2 through 7 PowerFlex 750-Series drives.

Step 5 – Choosing the Dynamic Brake Resistance Value

To avoid damage to this transistor and get the desired braking performance, select
a resistor with a resistance between the maximum resistance calculated in Step 3
and the minimum resistance of the drive IGBT.

Frame

400V

480V

ND kW

Catalog Code

Min Resistance

Max DB Current

ND HP

Catalog Code

Min Resistance

Max DB Current

2

0.75

C2P1

31.6 25

1.0

D2P1

31.6

25

1.5

C3P5

31.6

25

2.0

D3P4

31.6

25

2.2

C5P0

31.6

25

3.0

D5P0

31.6

25

4.0

C8P7

31.6

25

5.0

D8P0

31.6

25

5.5

C011

31.6

25

7.5

D011

31.6

25

7.5

C015

31.6

25

10

D014

31.6

25

11

C022

22.6

34.9

15

D022

22.6

34.9

3

15

C030

31.6

25

20

D027

31.6

25

18.5

C037

31.6

25

25

D034

31.6

25

22

C043

16.6

47.6

30

D040

16.6

47.6

4

30

C060

15.8

50

40

D052

15.8

50

37

C072

15.8

50

50

D065

15.8

50

5

37

C072

7.9

100

50

D065

7.9

100

45

C085

7.9

100

60

D077

7.9

100

55

C104

7.9

100

75

D096

7.9

100

6

55

C104

3.3

239.4

75

D096

3.3

239.4

75

C140

3.3

239.4

100

D125

3.3

239.4

90

C170

3.3

239.4

125

D156

3.3

239.4

110

C205

3.3

239.4

150

D186

3.3

239.4

132

C260

3.3

239.4

200

D248

3.3

239.4

7

132

C260

2.4

329

200

D248

2.4

329

160

C302

2.4

329

250

D302

2.4

329

200

C367

2.4

329

300

D361

2.4

329

250

C456

1.65

478.8

350

D415

1.65

478.8

Advertising
This manual is related to the following products: