Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 109

Advertising
background image

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

109

Feedback and I/O

Chapter 2

Example 4

P255 [Anlg In Type], Bit 0 = “1” (Current)

P545 [Spd Ref A Sel] = “Analog In 1”

P547 [Spd Ref A AnlgHi] = 60 Hz

P548 [Spd Ref A AnlgLo] = 0 Hz

P61 [Anlg In1 Hi] = 20 mA

P62 [Anlg In1 Lo] = 4 mA

This configuration is referred to as offset. In this case, a 4…20 mA input signal
provides 0…60 Hz output, providing a 4 mA offset in the speed command.

Example 5

P255 [Anlg In Type], Bit 0 = “0” (Voltage)

P545 [Spd Ref A Sel] = “Analog In 1”

P547 [Spd Ref A AnlgHi] = 0 Hz

P548 [Spd Ref A AnlgLo] = 60 Hz

P61 [Anlg In1 Hi] = 10V

P62 [Anlg In1 Lo] = 0V

This configuration is used to invert the operation of the input signal. Here,
maximum input (10V) represents 0 Hz and minimum input (0V) represents
60 Hz.

20

18

16

14

12

10

8

6

4

2

0

0 10 20 30 40 50 60

Output Hertz

Inp

ut mA

10

9

8

7

6

5

4

3

2

1

0

0 10 20 30 40 50 60

Output Hertz

In

pu

t V

ol

ts