Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 3

Diagnostics and Protection

Figure 18 - PWM Voltage at the Drive Output Terminals

Ideally, the voltage waveform at the motor looks exactly the same as the output of
the drive. However, the voltage at the motor has individual on/off pulses that
make up the PWM voltage waveform along with a ringing that occurs at every
switching transition. This is shown in

Figure 19

. The peaks of the ringing

waveform can easily reach two times the peak of the voltage pulses at the drive
(the DC bus voltage). After a short time, the ringing dies away and the motor sees
the normal DC bus voltage level. It is this peak level of the ringing voltage that
causes motor failure.

Figure 19 - PWM Voltage at the Motor Terminals

Shorten the time sweep or magnify these pulses and the ringing effect at the
motor terminals can be seen.

DC Bus Volts

0 Volts

2X to 4X Voltage Spike

0 Volts