Rockwell Automation 20G PowerFlex 750-Series AC Drives User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 750-RM002B-EN-P - September 2013

Chapter 1

Drive Configuration

With bus regulation disabled, the bus voltage can exceed the operating limit and
the drive faults to protect itself from excess voltage.

With bus regulation enabled, the drive can respond to the increasing voltage by
advancing the output frequency until the regeneration is counteracted. This
keeps the bus voltage at a regulated level below the trip point.

The bus voltage regulator takes precedence over acceleration/deceleration.

Select bus voltage regulation in the Bus Reg mode parameter.

Drive Output Shut Off

0V Fault @ V

bus

Max

DB Bus

Motor Speed

Output Frequency