Selecting a module input type, Communicating with your module – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 12

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

2 About POINT I/O Modules

Selecting a Module Input
Type

The 1734-IT2I module consists of two isolated millivolt inputs (+70 mV).
Configure the module to do the linearization necessary for thermocouple
inputs. See the table for a list of supported thermocouple input types.

The 1734-IR2 consists of two RTD inputs (0...600 W). Configure the module
to do the linearization necessary for RTD inputs. See the table for a list of
supported input types.

The 1734-IR2E consists of two RTD inputs (0...200 W). Configure the module
to do the linearization necessary for RTD inputs. See the table for a list of
supported input types.

Communicating with Your
Module

I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s
memory. The Thermocouple input module produces 8 bytes of input data
(scanner Rx) and fault status data. It does not consume I/O data (scanner Tx).

The RTD input module produces 6 bytes of input data (scanner Rx) and fault
status data. It does not consume I/O data (scanner Tx).

Supported Sensor Types – Thermocouple

mV (default) -70...+70 mV

B

572...3272 °F

(300...1800 °C)

C

32...4199 °F

(0...2315 °C)

E

-418...+1832 °F

(-250...+1000 °C)

J

-346...+2192 °F

(-210...+1200 °C)

K

-418...+2502 °F

(-250...+1372 °C)

N

-418...+2372 °F

(-250...+1300 °C)

R

32...3214 °F

(0...1768 °C)

S

32...3214 °F

(0...1768 °C)

T

-418...+752 °F

(-250...+400 °C)

Supportted Sensor Types – RTD

100 Pt

α

= 0.00385 Euro

-328...1598 °F

(-200...+870 °C)

200 Pt

α

= 0.00385 Euro

-328...1166 °F

(-200...+630 °C)

100 Pt

α

= 0.003916 U.S.

-328...1166 °F

(-200...+630 °C)

200 Pt

α

= 0.003916 U.S.

-328...1166 °F

(-200...+630 °C)

10 Cu

α

= 0.00427

-328...500 °F

(-200...+260 °C)

100 Ni

α

= 0.00618

-76...+482 °F

(-60...+250 °C)

120 Ni

α

= 0.00618

-76...+482 °F

(-60...+250 °C)

120 Ni

α

= 0.00672

-76...+482 °F

(-60...+250 °C)

Advertising