Calibrate Your Module

Overview

Use this chapter to calibrate the thermocouple/mV module or the RTD input
module. Refer to the table for a summary of what is covered.

When and How to Calibrate
Your Module

Your module is shipped to you already calibrated. If a calibration check is
required, the module must be in a POINT I/O system.

Perform module calibration periodically, based on your application. Module
calibration may also be required to remove module error due to aging of
components in your system.

Calibration Method

Perform calibration through the I/O configuration software, such as
RSNetWorx and EDS files. If the EDS files are not in your software, get them
online at

www.ab.com/networks/eds/

.

Tools and Equipment
Required to Calibrate
Your Thermocouple Module

To calibrate your thermocouple module, you need the following tools and
equipment.

Task

Page

When and How to Calibrate Your Module

39

Calibration Method

39

Tools and Equipment Required to Calibrate Your Thermocouple Module

39

Calibrate the Thermocouple Input Module

40

Input (mV) Calibration

42

Cold Junction Compensation Calibration

45

Tools and Equipment Required to Calibrate Your RTD Module

48

Calibrate the RTD Input Module

48

Tool or Equipment

Description

Precision Resistors

High precision resistors:

1000

Ω

, 0.05%, 5 ppm/

o

C

3000

Ω

, 0.05%, 5 ppm/

o

C

or
Calibrated resistor Decade Box, 0.05%

Precision Voltage Source

+100 mV, 1 mV resolution - accuracy +3

μ

V or better