Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 56

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

46 Calibrate Your Module

2. Click Calibration Command and select Begin CJC Calibration.

3. Click the Download to Device button.

4. Using a 1734-RTB removable terminal block, apply 1000

Ω

to the

selected CJC channel, referring to the wiring diagram in this section.

5. Select Accept Low CJC and download to the device.

6. Using a 1734-RTB removable terminal block, apply 3000

Ω

to the

selected CJC channel.

Click calibration
command and select
Begin CJC calibration.
Then download to the
module.