Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 68

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

58 Configure Modules in RSLogix 5000 Software

2. Make entries on the dialog, referring to the table for information on

how to complete entries for the channel indicated.

For details on these parameters see the Configure Your RTD Input
Module section on page 31.

3. From the bottom of the dialog, perform one of the following:

• Click a tab at the top of the dialog to continue making entries.
• Click OK to save changes and close the dialog.
• Click Cancel to return to default values.
• Click Apply to save changes you made on any of the dialogs and

continue to display the dialog, noting that you enable the Apply
button when you make changes to any of the dialogs.

For This Value

Select

Comments

Sensor Type

Ohms
100

Ω

Pt 385

200

Ω

Pt 385

100

Ω

Pt 3916

200

Ω

Pt 3916

10

Ω

Cu 427

120

Ω

Ni 672

100

Ω

Ni 618

120

Ω

Ni 618

Default is 100

Ω

Pt 385.

(The 1734-IR2E module only supports
Ohms, and 100

Ω

Pt 385)

Temperature Units

Custom Scale
Celsius
Fahrenheit
Kelvin
Rankine

Default is Celsius.

High Engineering

Select from
-32,768...32,767.

Default is 5000.
This is enabled when you select Custom
Scale for Temperature Units.

Low Engineering

Select from
-32,768...32,767.

Default is 1000.
This is enabled when you select Custom
Scale for Temperature Units.

Digital Filter (ms)

Select from 0...10,000.

Default is 0.

Notch Filter

50 Hz
60 Hz
100 Hz
120 Hz
200 Hz
240 Hz
300 Hz
400 Hz
480 Hz

Default is 60 Hz.

TIP

The 1734-IR2E can display temperature in tenths. Choose
Custom Scale, and set low scaling to 0, and high scaling
to 3000.