40 Calibrate Your Module

Calibrate the Thermocouple
Input Module

To calibrate your thermocouple input module, connect the module in a
DeviceNet system similar to that shown in the figure.

Module Connection

IMPORTANT

Apply power to the power supply and module for at least 10
minutes before calibrating the module.

Delete all I/O connections by removing the module from its
master's scan list and inhibiting the module in RSLogix. When
there is no connection present the Network Status Indicator
should flash green.

0

1

0

1

0 1

0

1

0

1

0

1

0

1

DeviceNet Input

Precision
Voltage
Source

Channel 0
Connect to 4 and 5

Channel 1
Connect to 6 and 7

1734-IT2I

1734-PDN

Shield

0+

0-

1-

1+

Thermocouple 0

Thermocouple 1

Precision Voltage
Source

0+

1+

1734-RTB
CJC

1734-RTB

Precision resistors

0+

1+

0 -

1-

46001

45999

46011