Publication 1734-UM004F-EN-E - December 2012

54 Troubleshoot the Module

Chapter Summary

This chapter helped you to interpret the status indicators on the modules.
Refer to the Appendix to learn how to configure the POINT I/O
Thermocouple and RTD Modules using the RSLogix 5000 software.

Network status Off

Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status
indicator.

Flashing green

Device is online but has no connections in the
established state.

Green

Device online and has connections in the
established state.

Flashing red

One or more I/O connections are in timed-out
state.

Red

Critical link failure is present with failed
communication device. Device detected error that
prevents it from communicating on the network.

Flashing
red/green

Communication faulted device - the device
detected a network access error and is in
communication faulted state. Device received and
accepted an Identify Communication Faulted
Request - long protocol message.

Channel status

Off

Module is in CAL mode.

Solid green

Normal state is present with channel scanning
inputs.

Flashing green

Channel being calibrated.

Solid ged

Major channel fault is present.

Flashing ged

Channel is at end of range (over or under).

IMPORTANT

This module is not field repairable. Any attempt to open this
module will void the warranty. If repair is necessary, return this
module to the factory.

Indicator Sta

s

tus for Module

Status

Description