Publication 1734-UM004F-EN-E - December 2012

64 Configure Modules in RSLogix 5000 Software

Alarm Configuration Dialog

This dialog does not appear for Listen-Only options. The dialog displays alarm
configuration parameters for each channel in individual rows on the grid. To
complete entries on this dialog, proceed as follows.

1. Click Alarm Configuration to display the dialog.

Low Engineering

-32,768...32,767.

Default is 1000.
This is enabled when you select Custom
Scale for Temperature Units.

Digital Filter (ms)

0...10000.

Default is 0.

Notch Filter

50 Hz
60 Hz
100 Hz
120 Hz
200 Hz
240 Hz
300 Hz
400 Hz
480 Hz

Default is 60 Hz.

Cold Junction Enable

Click to check the
checkbox

If checked the Cold Junction feature is
enabled.

Cold Junction Offset
(°C)

0.00...70.00

Select a value to configure the value for
cold junction offset.
You enable this feature when you check
Cold Junction Enable.
This feature is disabled in Hard Run mode.
Default is 0.

Cold Junction Notch
Filter

50 Hz
60 Hz

Select the value for Cold Junction Notch
Filter.
Default is 60 Hz.

Cold Junction Mode

None
Channel 0
Channel 1
Average Both

Select a value for Cold Junction Mode.
Default is channel 0.

For This Value

Select

Comments