5 - troubleshoot the module, Overview, Interpret the status indicators – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 63: Chapter 5, Troubleshoot the module, Overview interpret the status indicators, Chapter

Advertising
background image

53

Publication 1734-UM004F-EN-E - December 2012

Chapter

5

Troubleshoot the Module

Overview

Read this chapter to interpret your I/O module status indicators.

Interpret the Status
Indicators

Each module has the following status indicators:

• Module
• Network
• Input 0
• Input 1

Status Indicators on the Module

Indicator Sta

s

tus for Module

Status

Description

Module status

Off

No power applied to device.

Green

Device operating normally.

Flashing green

Device needs commissioning due to missing,
incomplete, or incorrect configuration.

Flashing red

Recoverable fault is present.

Red

Unrecoverable fault may require device
replacement.

Flashing
red/green

Device is in self-test.

Thermocouple

Input

Module

Status

Network

Status

1734

IT2I

NODE:

0

1

RTD

Input

Module

Status

Network

Status

1734

IR2

NODE:

0

1

Module status

Network status

Status of input 0

Status of input 1

46000

46009