Configure your module – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 66

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

56 Configure Modules in RSLogix 5000 Software

Optimized Connections. They only support direct Data (default) and Listen
Only Connections.

When you change Connection and Data Format:

• you do not delete the existing module.
• you do not create a new module.
• you bring forward all possible configuration data for the new setting.
• configuration data that you cannot bring forward sets to the default

value.

Once you apply new settings, this becomes the base configuration for the next
change in Connection and Data Format settings. When you select Apply, you
lose all configuration data from previous data formats.

Configure Your Module

Perform this procedure to configure your module in RSLogix 5000 software:

1. Configure your adapter. Refer to the user manual for your adapter for

information on how to configure the adapter and add modules to the
I/O configuration to include the following:

• Select a controller
• Select a communication module

2. Add a 1734-IR2, 1734-IR2E or 1734-IT2I module, according to the

instructions in your adapter user manual.

3. Complete entries for the following dialogs, as explained in this appendix.

• Configuration
• Alarm Configuration
• Calibration

Module Connection Formats

Adapter Communication Formats

Possible Module Connection Formats

Listen Only - Rack Optimization

Data (default)

Listen Only

None

Data (default)

Listen Only

Rack Optimization

Data (default)

Listen Only

Advertising