Publication 1734-UM004F-EN-E - December 2012

Configure Your Module 31

Configure Your RTD Input
Module

Configuration is divided into basic and advanced parameters.

Basic Setup Parameters

The basic parameters you need to set for the RTD module consist of:

• Temperature units – Use the Temperature Scale parameter to select a

predefined scale or a custom scale. Custom Scale allows you to enter the
scaling endpoint values. If using Ohms RTD Type, ignore this
parameter. Predefined Scales include: Celsius(C), Fahrenheit(F),
Kelvin(K), and Rankine(R).
Scaling Endpoints for Custom Scale (low & high):

• RTD type – Select the RTD type that the input uses. Valid types are

shown in the table.

• Copper RTD Offset – If using the copper RTD, this is the error of the

Copper RTD (10

Ω

Cu427) in Ohms. Enter a value between -250 and

250 in hundredths of Ohms (such as 361 = 3.61

Ω

). This value is added

to the input reading before linearization.

RTD Module Scaling Limits

RTD Type

Low Scaling
Endpoint

High Scaling
Endpoint

Ohms

100

Ω

500

Ω

100

Ω

Pt

α =

0.00385 Euro

32 °F (0 °C)

932 °F (500 °C)

200

Ω

Pt

α =

0.00385 Euro

32 °F (0 °C)

932 °F (500 °C)

100

Ω

Pt

α =

0.003916 U.S.

32 °F (0 °C)

932 °F (500 °C)

200

Ω

Pt

α =

0.003916 U.S.

32 °F (0 °C)

932 °F (500 °C)

10

Ω

Cu

α =

0.00427

32 °F (0 °C)

482 °F (250 °C)

100

Ω

Ni

α =

0.00618

32 °F (0 °C)

482 °F (250 °C)

120

Ω

Ni

α =

0.00672

32 °F (0 °C)

482 °F (250 °C)

120

Ω

Ni

α =

0.00618

32 °F (0 °C)

482 °F (250 °C)

RTD Type (1734-IR2E)

Low Scaling
Endpoint

High Scaling
Endpoint

Ohms

100

Ω

200

Ω

100

Ω

Pt

α =

0.00385 Euro

32 °F (0 °C)

572 °F (300 °C)