Calibrate the rtd input module – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 58

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

48 Calibrate Your Module

Tools and Equipment
Required to Calibrate
Your RTD Module

To calibrate your RTD module, you need the following tools and equipment.

Calibrate the RTD Input
Module

To calibrate your RTD input module, connect the module to a DeviceNet
system similar to that shown in the figure and perform the following
procedures.

Module Calibration

1. Double-click the icon to bring up the General Parameter dialog.

Tool or Equipment

Description

Precision Resistors

High precision resistors:
100

Ω

, 0.04%, 5 ppm/ oC

500

Ω

, 0.03%, 5 ppm/ oC - for 1734-IR2 module

200

Ω

, 0.03%, 5 ppm/ oC - for 1734-IR2E module

or
Calibrated resistor Decade Box, 0.05%

Precision Voltage Source

+100 mV, 1 mV resolution - accuracy +3

μ

V or better

IMPORTANT

Apply power to the power supply and module for at least 10
minutes before calibrating the module.

0

1

0

1

0 1

0

1

0

1

0

1

0

1

DeviceNet Input

100

Ω

for Low;

500

Ω

for High

Channel 0
Connect to 0 and 2

Decade
Resistance Box
(0.05% or better)

Channel 1
Connect to 1 and 3

1734-IR2

1734-PDN

Channel 0

Channel 1

45998

45999

100

Ω

for Low;

500

Ω

for High

1

Ω

resistor

1

Ω

resistor