Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual

Page 53

Advertising
background image

Publication 1734-UM004F-EN-E - December 2012

Calibrate Your Module 43

1. From the Configuration tab, set the Thermocouple Type to mV (no

linearization) for the channel(s) to be calibrated and download to the
module.

2. Open the Device Parameter tab and click Calibration Channel Select to

bring up your channel selections.

3. Select a channel (0 or 1), or select Both Channels.

4. Click Download to Device.

For input calibration, choose:
Input Channel 0,
Input Channel 1, or
Both Channels.