Publication 1734-UM004F-EN-E - December 2012

Configure Your Module 21

The out-of-the-box node setting for 1734 modules is 63. You can change the
setting by using the node commissioning tool. The node commissioning tool is
available either online or offline.

1. Go to the Tools pull-down menu.

2. Select Node Commissioning.

3. Click Browse.

4. Select the module to change.

5. The node commissioning dialog

returns. It displays the node number
and data rate.

6. Change the node number and

Apply, noting that the dialog then
identifies the new setting.

7. Click Close to continue.

4

2

3

1

5

6

IMPORTANT

If you commission a node online, you must power down your
system before the change takes place.