Rockwell Automation Publication 7000-UM201B-EN-P - June 2013

19

PowerFlex HMI Interface Board

Chapter 2

Knowing this IP address, open a web browser and enter the IP address prefixed
with http://. This opens the web page for the HMI Interface Board module from
which the Forge Shell program is launched. Refer to

Set an IP Address with Forge

Shell on page 20

.

Using HyperTerminal

If the IP address of an existing module cannot be determined, connect to the
USB port of the HMI Interface Board module.

1.

Use a program such as HyperTerminal™ (usually supplied with the
Windows OS) to connect to the HMI Interface Board using the following
settings:

115,200 Baud

8-data bits

1-Stop bit

No parity

2.

Set the HMI Interface Board DIP Switch (SW2), switch 1 to ON. Refer to

DIP Switch Settings on page 81

.

3.

Press the reset button SW1 on the HMI Interface Board module.

The screen typical of

Figure 11

, shows the current configuration of the

HMI Interface Board module.

4.

After obtaining the IP address, place the DIP Switch (SW2) Switch 1,
back to the default position of OFF.

5.

Open a web browser and enter the IP address prefixed with http://

This opens the web page for the HMI Interface Board module from which
the Forge Shell program is launched (refer to

Set an IP Address with Forge

Shell on page 20

).

Figure 11 - IP Address via HyperTerminal

TIP

See

USB Port on page 83

for information on obtaining and installing USB

drivers for Windows XP and Windows 7.