Rockwell Automation 7000 PowerFlex HMI Offering with Enhanced Functionality User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 7000-UM201B-EN-P - June 2013

73

System Updates

Chapter 6

4.

Click Yes, and enter the appropriate PIN value for the desired access level.

5.

Press Enter on the keyboard.

A bar graph shows the progress of the file transfer to the HMI Interface
Board. A status window under the Update button shows information
about the update progress.

Once the entire Package has been downloaded, the HMI Interface Board
will perform a validation process on the contents.

Status strings provide information about each step in the process:

Validating each file

Extracting each file

Completion status

If any of the contents fails validation, or the drive is not in download mode
to accept an included .FFW file, the entire process will be aborted.

6.

Press Update.

TIP

The PIN codes required for the firmware download are the same PIN codes
used in the operator interface. Unless changed, the Advanced PIN is 0 by
default. If an incorrect PIN is entered, the update process must be restarted.