Prosonic M Ultrasonic Level

Appendix E

Connect a Prosonic M
Ultrasonic Level

Use a 2-wire connection to the HART input module.

1. Unscrew housing cover (1).
2. Remove display (2), if fitted.
3. Remove cover plate (3) from terminal compartment.
4. Pull out terminal module (4) slightly using pulling loop.
5. Insert cable (5) through gland (6).

6. Connect cable screen to the grounding terminal (7) within the terminal

compartment.

7. Make connection according to terminal assignment.
8. Re-insert terminal module (4).
9. Tighten cable gland (6).

10. Tighten screws on cover plate (3).
11. Insert display (2), if fitted.
12. Screw on housing cover (1).
13. Switch on power supply.

ATTENTION: If possible, insert the cable from above and let a draining loop in
order to avoid intrusion of humidity.