Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014

135

Prosonic S Transmitter

Appendix J

Signals from Instrument to Control System

Connect a Prosonic S
Transmitter

Use a 4-wire connection to the HART input module. Following are the terminals
of the Prosonic S. The terminals depicted in grey are not present in every
instrument version.

Output Signal

Details

Current Output

4...20 mA with HART
0...20mA without HART
USS = 200 mV at 47...125Hz (measured at 500

Ω)

Ueff = 2,2 mV at 500 Hz... 10 kHz (measured at 500

Ω)

For Setting 4...20 mA, selectable
10% (3,6 mA)
110% (22 mA)
HOLD (last current value is held)
User specific

For Setting 0...20 mA
110% (21,6 mA)
HOLD (last current value is held)
User specific

Maximum 600

Ω, influence negligible

USS = 200 mV at 47...125Hz (measured at 500

Ω)

Ueff = 2,2 mV at 500 Hz...10kHz (measured at 500

Ω)

Output Damping

Freely selectable, 0...1000 s

Relay Outputs

DC voltage: 35 VDC, 100 W
AC voltage: 4 A, 250 V, 100 VA at cos = 0.7

FDU-

Sensor

0/4...20mA

1

42

41

Relay

55

52

54

51

53

50

3

Address

T

erm.

DP

of

f

on

of

f

on

SW

HW

1
2
3
4
5
6
7
8

1
2
3
4

A(N)

66

B(P)

65

Display

POWER

HART

0/4…20mA

Sync

Fuse

I

1

FDU-

Sensor

RD

11

BK

10

YE

9

40

39

5

4

6

7

8

1

1

Service

Relay

3

2

1

A

B

C

E

2

58

57

56

4

61

60

59

5

64

63

62

6

RD

11

BK

10

YE

9

2

RD

14

BK

13

YE

12

I

2

FDU-

Sensor

DigIn

76

73

75

72

74

71

2

D

1

79

78

77

3

82

81

80

4

85

84

83

T

emp.

Item

Description

A

Basic terminal area

B…E

Optional terminal areas (present if the respective option has been selected in the product structure).