Promag 53 Electromagnetic Flowmeter

Appendix A

3. Connect the HART communications cable to the HART connector in

the order white (+), black (-) on pins 26, 27 of the connector.

4. For AC powered instruments, connect the AC cable to the power

connector in the order ground (as shown), black (pin1), white (pin2).

5. Screw the cover of the connection compartment (f ) firmly onto the

transmitter housing.

Item

Description

a

Cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC

b

Signal cable: Terminal Nos. 20-27

c

Ground terminal for protective conductor

d

Ground terminal for signal cable shield

e

Service adapter for connecting service interface FXA 193 (FieldCheck, FieldCare)

f

Cover of the connection compartment

g

Securing clamp

b

b

c

d

a

a

2
1

– 27

– 25

– 23

– 21

+ 26

+ 24

+ 22

+ 20

L1 (L+)

N (L-)

g

f

e