Rockwell Automation 1734sc-IE4CH E+H Instruments via HART to PlantPAx User Manual User Manual

Page 82

Advertising
background image

82

Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014

Chapter 5

Visualization

The faceplates provide the following information:

Tag name from instrument
Description from instrument
Engineering units from instrument
Typical analog process values (PV)
Analog fault status (channel fault, broken wire, module fault)
HART PV (first, second, third)
HART PV fault status (first, second, third, fourth)
HART PV range (minimum and maximum)
HART command 48 diagnostic information

Configure the faceplates to provide the following:

Mode (such as operator or program)
High-high, high, low, and low-low alarms
Over-range and under-range alarms
Alarm delay
Alarm hysteresis

IMPORTANT

A unique global object and faceplates are available for each field instrument
due to the display of instrument-specific diagnostic information.