Measured variables, Signals from instrument to control system – Rockwell Automation 1734sc-IE4CH E+H Instruments via HART to PlantPAx User Manual User Manual

Page 116

Advertising
background image

116

Rockwell Automation Publication PROCES-UM002A-EN-P - July 2014

Appendix G

Micropilot M Radar Level

Rod antenna with inactive length:

Reliable measurement in narrow nozzles, with condensation and build-up
in the nozzle.

Measured Variables

The measured variable is the distance between a reference point and a reflective
surface (i.e. medium surface). The level is calculated based on the tank height
entered. The level can be converted into other units (volume, mass) by means of a
linearization (32 points).

Signals from Instrument to Control System

Item

Description

E

Empty distance

F

Span (full distance)

D

Distance from sensor membrane - product surface

L

Level

20 mA
100%

4 mA
0%

D

L

F

E

flange:
reference point of
measurement

flange:
reference point of
measurement

inactive
length

max.level

threaded
connection
1 ½”

(R 1

:

reference point of
measurement

BSPT

½”)

or 1½ NPT

Signal

Details

Current Output

4...20mA with HART protocol