iTEMP TMT182 Temperature Transmitter

Signals from Instrument to Control System

Connect an iTEMP TMT182
Temperature Transmitter

Use a 2-wire connection to the HART input module.

Signal

Details

Output Signal

Analog 4...20mA, 20...4mA

Load

Max. (VPower supply - 11.5 V) / 0.022 A (current output)

Switch on Delay

4 s (during power up la - 3.8 mA)

Galvanic Isolation

U = 2 kV AC (input/output)

Signal on Alarm

Underranging:

Linear drop to 3.8 mA

Overranging:

Linear rise to 20.5 mA

Sensor break; sensor short-circuit (not for thermocouples TC):

3.6 mA or 21.0 mA
Failure signal 21.0 mA; if output setting is 21.0 mA,

>

21.5 mA is guaranteed

Allowable Ripple

Uss

3 V at Ub

13 V, fmax. = 1 kHz