Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual

Page 16

Advertising
background image

2-4

GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Program or
Monitor

When the control source is set to OIM, jogs the motor when held down (and the
drive is ready). The motor ramp stops when it is released.

When

is pressed, the motor ramps up to the JOG SPEED REFERENCE

(P.020) at the speed set by JOG RAMP ACCEL TIME (P.021). When it is
released, the drive ramps down to zero at the speed set by JOG RAMP DECEL
TIME (P.022).

Program or
Monitor

When the control source is set to OIM, applies power to the motor.

is

only active if the drive ready indicator is on.

Program or
Monitor

If the drive is running, the drive is stopped as selected by STOP TYPE (P.025).

When the OIM is connected and communicating with the drive,

is active,

regardless of the control source.

If the drive is not running and the control source is set to OIM,

resets any

active faults. See chapter 7 for more information on resetting faults.

Refer to the P.055 (STOP/RESET Key Disable) parameter description in the

software I/M for more information about

.

Table 2.2 – Control Key Descriptions (Continued)

Key

Mode

Function

!

ATTENTION: Pressing

on the OIM immediately starts the

motor if the control source is set to OIM. Make sure the motor and
driven machinery are safe to start before pressing this key. Failure
to observe this precaution could result in severe bodily injury or
loss of life.

!

ATTENTION: Pressing

on the OIM immediately starts the

motor if the control source is set to OIM. Make sure the motor and
driven machinery are safe to start before pressing this key. Failure
to observe this precaution could result in severe bodily injury or
loss of life.

!

ATTENTION: When P.055 is set to ON,

is functional only from

the selected control source. As a safety precaution, Reliance
Electric recommends that an emergency stop push button be
located near the drive in an easily accessible location. As a further
safety precaution, the user should post a warning on the drive to
alert personnel that

is not functional. Failure to observe this

precaution could result in severe bodily injury or loss of life.

ATTENTION: The user must provide an external, hardwired
emergency stop circuit outside the drive circuitry. This circuit must
disable the system in case of improper operation or OIM failure.
Uncontrolled machine operation can result if the procedure is not
followed. Failure to observe this precaution could result in bodily
injury.