Troubleshooting the Drive Using the OIM

7-7

Step 2. If the DRIVE READY indicator is off, the drive is not ready to start. If this is

the case, move the cursor to “Why is the drive not ready?” and press

.

The screen shows possible explanations of why the drive is not ready. If the

symbol is displayed, more information is available. Press

to read the

rest of the screen. Table 7.1 lists all possible responses.

Step 3. Press

to exit the screen.

Step 4. Press

again at the Diagnostics Menu to return to program or monitor

mode.

7.5

Clearing a Programming Error Screen

Programming errors occur if you select an option that is not valid, such as attempting
to set a read-only parameter. These errors do not affect drive operation and are not

logged. To remove the programming error message, press

.

Table 7.1 – Possible OIM Responses to “Why is the Drive Not Ready?”

Display

Description

PRE-CHARGE IS NOT READY

The DC bus is not within required tolerance.

FP STOP ACTIVE

The front-panel STOP key is asserted.

SERIAL STOP ACTIVE

The serial port (CS3000) stop input is
asserted.

ACTIVE CS STOP ACTIVE

The active control source stop input is
asserted.

DRIVE NOT IDENTIFIED

The Power Module has not been identified to
the regulator.

DOWNLOAD IN PROGRESS

The CS3000 configuration download
procedure is in progress.

COAST/DB STOP OPEN

The coast/DB stop input (TS 23) is open.

CUSTOMER INTERLOCK OPEN

The function loss input (TS 20) is open.

MEMORY OPERATION IN
PROGRESS

Non-volatile memory is being restored.

DRIVE IS IN PROCESS OF
STOPPING

The drive is in the process of stopping.

THERE IS A DRIVE FAULT(S)

The drive is faulted.

THE DRIVE IS READY.

The drive is ready to run.

A STOP INPUT IS ACTIVE

A keypad stop key or the selected control
source stop input is asserted.