4 using diagnostics to troubleshoot drive problems – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual

Page 65

Advertising
background image

7-6

GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Step 2. Select Review Active Alarms by pressing

. A sample of the screen is

shown in figure 7.7.

Step 3. Move the cursor to the alarm you would like more information on. Press

. The alarm detail screen for that alarm is displayed. If the

symbol is

displayed, more information is available. Press

to read the rest of the

screen.

Step 4. Press

to the Alarm Menu.

Step 5. Press

again to return to program or monitor mode.

The alarms are cleared from the review screen when the situation that caused the
alarm is resolved.

7.4

Using Diagnostics to Troubleshoot Drive Problems

The Diagnostics Menu provides information on why the drive is not ready. The
diagnostics screen is continually updated with the status of the drive.

To use diagnostics:

Step 1. Press

until the key indicator reads DIAGS. The Diagnostics Menu

screen is displayed, as shown in figure 7.8.

Figure 7.7 – Review Active Alarms Screen

Figure 7.8 – Diagnostics Menu