Hardy control link network mapping, Devicenet output, Plc hi 3010/devicenet – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 92: Mapping to the devicenet light bar

Advertising
background image

HI-3010 Filler/Dispenser/IBC

76

Service Manual

FIG. 6-40 DEVICENET OUTPUT

FIG. 6-41 DEVICENET OUTPUT

Hardy Control Link Network Mapping

If an HI 3010 Node #1 does not have any Output Relays
available, you can select another node’s Output Relay. HI
3010, Node #2 has an output relay available. This requires
that you first map Node #1 and Node #2 separately so that
the input contact in Node #1 can be mapped directly to the
Output Relay in Node #2. (See Fig. 6-42)

Step 2. You need to set up communication between Node

#1 and Node #2. You can do this by going to the HI
3010 Web Page, select Configuration, select Hardy
Control-Link. For complete instructions to setup
communications between instruments go to the HI
3000 Installation and Operation manual, Hardy
Control-Link Ethernet Network, Setting Node
Addresses for HI 3000 Series Instruments from the
Browser.

Step 3. At node #2 you need to map the Output Relay #3

state value, in the Output Image Table to the Hardy
Boolean In address in the Input Image Table. (See
Fig. 6-42 Green Arrows)

Step 4. At node #1 you need map Input Contact #1 in the

Input Image Table to Hardy Boolean Out in the
Output Image Table. (See Fig. 6-42 Red Arrows)

Step 5. Now that you have set up the local mapping for

Node #1 and Node #2 and Node #1 is communicat-
ing with Node #2 you can map the Input Contact at
Node #1 directly to the Output Relay at Node #2.
(See Fig. 6-42 Black Arrow)

PLC

HI 3010/DeviceNet

Input Image

Table

Output Image

Table

Node #1

Input Image

Table

Output Image

Table

0

1

2

3

Output

Boolean Word 11

OK To Fill

Mapping to OK to Fill on HI 3010

HI 3010/DeviceNet

Input Image

Table

Output Image

Table

Node #1

0

1

2

3

Output

Boolean Word 3

TOL Alarm

Mapping to the DeviceNet Light Bar