Profibus-dp .gsd file, Pre-initialization procedures – Hardy HI 6500 Series User Manual

Page 57

Advertising
background image

Network Configuration 49

Profibus-DP .GSD File All devices connected to a Profibus-DP network require a *.gsd
file. The *.gsd file contains all the parameters including the baud rate, table formats and
necessary data required by the network PLC when an HI 6500 or HI 6510 is connected to
the network.

You must download the proper *.GSD file from the Hardy website.

Step 1. Navigate from the products section to the HI 6500 web page.

Step 2. Click on the Tab, Docs & Programs and scroll down to Documents and Programs.

Select the *.GSD option to download the file.

Regardless of Simatic Manager you use, you must go through these three steps:

Step 1. Connect the HI 6500 Series Instrument to the Profibus DP network and verify the

address. (See the Installation Section for Installation and Cabling Instructions.)

Step 2. Step 2. Connect the PC to the Trunk Line. Load the configuration properties to the

initialization software on the PC and transfer them to the PLC.

Step 3. Step 3. Install the *.gsd file.

Pre-Initialization Procedures

Step 1. Inspect the network cables and make sure that the cables have been installed

correctly and satisfy the Profibus-DP guidelines for the data transmission baud
rate(s) required. (See the Cabling Chapter/Profibus Installation in this manual for
Profibus-DP cable specifications and cabling guidelines.)

Step 2. Select the Node address for the HI 6500 or HI 6510. as shown above. This can be

done before or after Initialization.

Step 3. Cycle power, or perform the two previous steps before powering up your network.

Address selection can only occur after cycling the power. Make sure that the
software you use will detect the values as you have set them.

Step 4. Complete any additional configuration that is required by your PLC for

initialization. Our initialization example is for a Siemens PLC. Your PLC
initialization requirements may differ.

CAUTION: The address should never be changed during operation. if the address is
modified while on line, an internal error could be generated and the instrument
disconnected from the network.

ATTENTION L’adresse ne devrait jamaisêtre changée durant le
fonctionnement. Si l’adresse est modifiée pendant la miseen ligne, une erreur
interne pourrait être créée et le module sera déconnecté du réseau.