Configuring profibus from the front panel, Initialization procedures on the plc – Hardy HI 6500 Series User Manual

Page 58

Advertising
background image

50 Chapter

4

Step 5. Install the *.GSD file for the instrument you connected to the Profibus

Network.

Configuring Profibus from the Front Panel

Step 1. Press the Configuration key

Step 2. Down arrow to Communications; press enter.

Step 3. Select Profibus-DP; press enter.

Step 4. Select Termination; press enter

Step 5. Up or down arrow to make termination selection. Press enter to select.

Step 6. Down arrow to select Serial Option;

Step 7. Press enter to toggle between Profibus-DP and Modbus. Select Profibus-DP and

press enter.

Step 8. Down arrow to Node.

Step 9. Press enter to make changes to the Node. Use the arrow keys to enter node number

and press enter to accept.

Step 10. Press exit key until display returns to the Summary Display.

Initialization Procedures on the PLC

NOTE

The examples come from the Siemens Step 7™, Simatic Manager Software. Your software
will vary from these procedures. Step 7™ is a trademark of the Siemens Corporation.

Step 1. Step 1. In the Siemens Step 7™, Simatic Manager, open the Hardware Catalog.

Step 2. Click on the “+” to expand the Additional Field Devices Folder.