Step 1. Insert the USB stick into the HI 6500 series instrument

Step 2. Using the web interface or display panel, save or restore system parameters.

Communications Parameters for the HI 6510 Only

Analog 4-20mA

Available on the HI6510 only

The analog 4-20mA output is directly proportional to the programmed gross, net, or count
range; by setting the low value equal to 4mA and the high value equal to 20mA. These
values can be set from either the front panel or the web interface.

The 4-20mA parameters can be configured through the web interface or the display panel.

From the front display: select the configuration menu then UP or DOWN to
communications, enter; UP or DOWN to 4-20mA, enter; UP or DOWN to setting you
want for Source; enter the value for 4mA; enter the value for 20mA or mA output (read
only). Press enter to select and UP or DOWN arrows to enter value.From the Website,
select the Communications Menu and then

Step 1. Select the source for the 4 to 20mA output, default is gross

a. Gross.

b. Net

c. Count

d. Manual

Step 2. Set the 4mA value