5. Complete other wiring to 5200A.

6. Close front panel -page 40.

7. Test relays.

Wiring a Contactor

The four onboard relays are rated at 240VAC@5AMPs (110VAC@10AMPs) switch-

ing capacity. Contactors should be used for devices drawing current loads higher

than relay specification. See figure 3.20 for contactor wiring.

Note:

- Contactor must meet the electrical requirements of the load.

Installation and Wiring

Installation and Wiring

Blower

X

Contactor

Contacts

Coil

YSI 5200A contactor wiring

Power for Blower

Power for Contactor

Switched Power

wire contactor power to “C” pin
wire second wire to “NC”/”NO” as required for application

Figure 3.20

Test Relay Outputs

Apply power to 5200A. Verify device activates at relay test. See Relay Test - page 127.

Note:

Entering the relay test menu turns off any active relays and disables any sensor,

aux, and timer system relays from energizing regardless of the value or condition.

Systems are not reset when the Relay Test menu is exited. To reset the systems after

exiting the Relay Test menu, power cycle the 5200A.

Step 6 Wire Aux Inputs

The 5200A has two auxiliary (aux) inputs. Aux inputs can be used for digital (open/

closed dry contacts) or analog (0-1VDC, 0-5VDC , or 4-20mA) inputs. Aux inputs

can be used for a variety of applications including: level switch, pressure switch,

and/or an external instrument with an analog recorder output. Aux input wires are

terminated at location K - figure 3.21. (See 5200A I/O board wiring diagram on

inside of front panel for identification of aux system number and pin position.) See

Digital Input example - figure 3.22 and Analog Input example - figure 3.23.