E 140), r, E 140) a, E 140). th – YSI 5200A User Manual

Page 71

Advertising
background image

YSI 5200A

141

YSI 5200A

140

AquaManager includes a PID Tuning tool which allows simulation of various control

action values and functions. The PID tuning tool should be helpful in mimicking

your system through simulation. The AquaManager PID Tuning tool is explained

in detail in the AquaManager Help System.

PID/PWM Interval control action

Range 1.00 to 999 (seconds)

Configure the interval control action to be the length of time a complete PID/PDW

control cycle takes. The control cycle includes both the control relay output on time

and the control relay output off time. Example: A 10 second control relay on time and

a 10 second control relay off time would represent a 20 second interval time. The 10

second control relay on time would be expected to decrease as the value reaches set

point. Interval, Reset interval and Gain control configurations are all interrelated in

the calculation of the control relay on time as the algothrium calculates the proper

corrective action.

PID/PWM Reset Interval control action

Range 0.00 to 100 (seconds)

Configure the Reset control action to be the rate at which the PID/PWM cycle re-

sets. In other words at what interval the past errors are erased and the PID/PWM

process begins a new cycle using new errors, and not past errors, in the PID/PWM

formula in calculating corrective action. Interval, Reset interval and Gain control

configurations are all interrelated in the calculation of the control relay on time as

the algothrium calculates the proper corrective action.

PID/PWM Gain control action

Range 0.01 to 10 %.

Gain is used to control the percentage of change in the output. Output increases with

greater gain. A high gain results in a large change in the output for a given change

in the error. A gain of “5” results in an additional 5% output relay on time for each

1% increase/decrease of the measurement. Tuning theory and industrial practice

indicate that gain should contribute the bulk of the output change. Interval, Reset

interval and Gain control configurations are all interrelated in the calculation of

the control relay on time as the algothrium calculates the proper corrective action.

PID/PWM Alarm System

Alarm values set the acceptable control range. Enable and configure system(s) alarm

to activate alarm output devices(s), view alarm icons, hear audible alarm and/or

receive alarm notifications sent via email or cell phone (SMS) - page 95. Config-

ure high and low alarm values to set alarm thresholds. Alarm system(s) becomes

Configuring the 5200A

active when value is ≤ low alarm value or ≥ high alarm value. Enabled alarm relays

energize if alarm condition exists for the general alarm hold off time. Alarm relays
are energized until one of the four softkeys

is pressed

regardless of sensor value. Pressing one of four softkeys resets the alarm system.

Alarm systems become active again if, after the alarm hold off period, the alarm

condition still exists. Alarm hold off is configured in the General Alarm menu.

When the General Alarm is enabled, (with or without enabled relay), the general

alarm system becomes active when any system alarm is active. See General Alarm

- 117.

Notes:

- It is important to keep the 5200A at the Run Screen during normal

operation. Alarm functionality (email alarms, activation of enabled

alarm relays, alarm icons, and buzzer) is suspended when 5200A is

not at Run Screen.

- Alarm icon(s) display at the Run Screen when alarm condition(s) exists

for longer than the general alarm hold off time. See Icons - page 70.

- Press

at Run Screen to display active sensor and aux system relays.

-

to display events created by control and alarm relays - see Event

Log - 107.

- Alarm relays are not energized if the 5200A sensor value reads “Over”

or “Under.”

- See Wire Relays - page 46 for information on wiring alarm output

devices.

30 Second Aux and Sensor System Hold Off

Exiting aux and sensor menus after making certain configuration changes places the

system in a 30 second hold. During the 30 second sensor hold, control and alarm

systems are not active. System(s) becomes active, if, after 30 seconds, the values

are reported in control or alarm range. This 30 second hold off allows sensors and

aux devices time to stabilize before control and/or alarm systems become active.

Example - conductivity sensor menu is entered when dose up system is active and

control relay is energized. Dose up wait time is changed from 15 seconds to 45
seconds. When

to Run Screen is pressed, the conductivity system dose up

wait time is saved. Dose up relay de-energizes regardless of sensor value. Dose up

control relay re-energizes if, after 30 seconds, the value is still in control low range.

Dose up relay will energize for the new configured dose up time.

Configuring the 5200A

Advertising