Step 7 wire network – YSI 5200A User Manual

Page 27

Advertising
background image

YSI 5200A

53

YSI 5200A

52

Wire Aux Digital Input

1. Install aux digital device according to manufacturer’s instructions.

2. Connect switch wires to Aux Input 1 or 2. Connect one wire at (G) at K. Connect

second wire to (1) or (2) at K.

Float
Switch

Auxiliary Input
Connector

CAUTION

:

Do not input external voltage.

Figure 3.22

Wire Aux Analog Input

1. Install analog instrument according to manufacturer’s instructions.

2. Connect analog instrument wires to Aux Input 1 or 2. Connect negative wire to

ground (G) at

K

.

Connect positive wire to (1) or (2) at

K.

Instrument with analog
voltage or 4-20 mA output

Auxiliary Input
Connector

+ -

CAUTION

:

Observe correct polarity on analog input.

Figure 3.23

Installation and Wiring

Step 7 Wire Network

Multiple 5200A, 5400 and 5500D-1, 5500D-2, 5500D-4 instruments can be net-

worked using the RS485 network ports. A node network consists of one master and

up to 31 slaves. On a network, the master is the point of access for the AquaManager

PC software program. In addition, the master sends all serial to ethernet device

emails. Communication hardware (RS232 or serial to ethernet device) is installed

on the master instrument (node) only.

RS485 network wiring can span distances up to 4000 feet (1220m). This maximum

distance (4000 ft) is for the total network distance, not the distance between net-

worked units (*see Notes below). RS485 ports are optically isolated for safety, to re-

duce noise, and to help eliminate ground loops. No further isolation is required.

Network traffic refers to the constant communication between the master and all

the slaves on the network. For example, slave node 3 is configured to generate an

alarm if the temperature drops below 70°F. The master node is configured to send

alarm emails via TCP/IP using the serial to ethernet device. The master node sends

an email alarm when slave node 3 reports a temperature value below 70° F (after

alarm hold off time) to the master.

AquaManager is a valuable tool for monitoring and controlling node networks.

Notes:

- *Use an RS485 Line Extender/Booster for distances over 4000’ (1220m).

Communication failures may occur without it. Mount the booster in an

area where it is protected from moisture.

- Multiple networks connected to a PC via RS232 require separate PC COM

ports for simultaneous AquaManager mapping and autopolling.

- Legacy 5200s can not be on the same network as 5200As, 5400s or 5500D-

1, 5500D-2 and/or 5500D-4 instruments. However, Legacy 5200s can

communicate with AquaManager and Legacy 5200 data will be stored in

the same database as 5200A, 5400, 5500D-1, 5500D-2 and 5500D-4 data.

- Network traffic speed operates at ~ 230 KB and is not user selectable.

- Remove network terminal strip from any networked slave that is not

powered. Network rewiring is required if a stub (*see next note) is cre-

ated when a slave is taken off the network. See valid network configura-

tion - figure 3.28

Note:

- *A stub is created when the last wired network terminal strip is not con-

nected to a network slave - figure 3.24.

Installation and Wiring

Advertising