SSi Manual Series 9010 – eSPP Programmer

Page 42

Wait


When using the option wait with a set point Opcode, the recipe will not advance to the next step until the
PV value falls within the wait limit band. The upper limit of this band is value of the PV set point plus the
wait limit. The lower limit of this band is the value of the PV set point minus the wait limi. The wait limit
band is the range between the upper limit and the lower limit. The recipe will then continue to the next
step. The atmosphere and temperature wait limit options are located in the Menu under Furnace Setup.

For example, assume the PV is temperature with a 1500° set point and a wait limit of 15°. Using the
SETPT opcode, if the option is wait, the recipe will not advance until the temperature PV is 1485°-1515°.