Humidity, Cleanliness – H3C Technologies H3C S12500-X Series Switches User Manual

Page 11

Advertising
background image

3

To ensure the normal operation of the switch, make sure the room temperature meets the requirements

in

Table 1

.

Table 1 Temperature requirements

Temperature Range

Operating temperature

0°C to 45°C (32°F to 113°F)

Storage temperature

–40°C to +70°C (–40°F to +158°F)

Humidity

Maintain appropriate humidity in your equipment room, as described in

Table 2

.

Lasting high relative humidity can cause poor insulation, electricity creepage, mechanical property
change of materials, and metal corrosion.

Lasting low relative humidity can cause washer contraction and ESD and cause problems including
loose mounting screws and circuit failure.

Table 2 Humidity requirements

Humidity Range

Operating humidity

5% to 95%, noncondensing

Storage humidity

5% to 95%, noncondensing

Cleanliness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal

components and contact points. In the worst case, electrostatic adsorption can cause communication

failure.

Table 3 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/m

3

)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in

Table 4

.

Table 4 Harmful gas limits in the equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05