2.2 Testing

Communications

Background

Once you connect power and the SCT or SFC to the transmitter, you are
ready to test communications with the transmitter.

Procedure

The procedure in Table 2 outlines the steps using an SFC for initiating
communications with an ST 3000 transmitter without an assigned tag
number.

Table 2

Testing Communications with Transmitter.

Step

Press Key

Read Display or Action

Description

1

Slide power switch on left side of SFC to
ON position.

SFC runs its self check and displays
initial prompt.

2

P U T

I N

M A N

L O O P

OR


D E

X

T

M

R

R E

S

I

S

P

D

If this prompt appears, transmitter is
in Analog mode of operation. This is
the factory default mode of
operation setting. Put your control
loop in the manual mode of
operation before initiating SFC
communications. Note that you must
do this separately through the
receiving device in the loop.

If this prompt appears, transmitter is
in Digital (DE) mode of operation.

3

DE READ

A

ID

T A

O

N

.

G

?

T R I P S

S E C U R E D ?

OR

Go to Step 5

Be sure any switches that may trip
alarms or interlocks associated with
analog loop are secured or turned
off. Go to Step 4.

This prompt does not appear for
transmitters operating in DE mode.
See DE transmitter display response
in Step 5.

4

NON-VOL

ENTER

(Yes)

Confirms that “TRIPS” are secured. Go
to Step 5 for display response.

Required for transmitters operating
in analog mode only.

Continued on next page

2/05

ST 3000 Release 300 Installation Guide