2 testing communications – Honeywell ST 3000 User Manual

Page 18

Advertising
background image

2.2

Testing Communications,

Continued

Procedure, continued

Table 2

Testing Communications with Transmitter, Continued

Step

Press Key

Read Display or Action

Description

5

T A

O

N

.

G

S F C

W O R K I N G . .

.

L

I N

A G

N O .

D P

T

_

OR





D E

X

T

M

T A

O

G

.

R

N

_

OR

T A G

O

O

R

X

T

O

N

M

E S

N

.

N S

R

P

E

Message exchange is taking place
Note that communications with
transmitter are blocked until [

ID

] key

is pressed

Transmitter is in analog
transmission mode. “LIN” means
transmitter is set for linear output
instead of square root (SQRT). “DP”
means transmitter is differential
pressure type instead of gauge
pressure (GP) or absolute pressure
(AP). Last eight columns in bottom
row are blank when no tag number
has been assigned to this
transmitter. Go to Step 8.

Transmitter is in digital (DE)
transmission mode. Last eight
columns in bottom row are blank
when no tag number has been
assigned to this transmitter. Go to
Step 7.

Communication error messages are
cycled at two second intervals and
display returns to initial prompt. Go
to Step 6.

6

There is a communication problem,
check the
• power and SFC connections - Is the

polarity correct; red to positive and
black to negative?

• loop resistance - Is there a minimum

of 250 ohms resistance between the
SFC and the power supply?

• power supply - Is power applied, is

there greater than 11 volts at the
transmitter, and are you within the
operating area on the curve in Figure
13?

Correct any wiring, resistance, or
power supply problems, and try
communicating again - Press [

ID

]

key.
If you are still not getting the
correct display, note error
messages and refer to
Troubleshooting section in the
transmitter’s User’s Manual 34-ST-
25-14
for probable cause.

Continued on next page

8

ST 3000 Release 300 Installation Guide

2/05

Advertising