A.8

Typical Smart Meter Indications

Typical operation
indications

Table A-10 summarizes typical smart indications. meter Note that other
combinations of status messages are possible.

Table A-10

Summary of Typical Smart Meter Indications.

Meter Indication

What It Means

Meter Indication

What It Means

%

100

0

No power

applied.

%

100

0

- - -

Meter has

detected

transmitter output

that is not-a-

number.

%

100

0

20

ANALOG

In H O

2

0

Normal display

for transmitter in

Analog mode

with digital

readout in

inches of water.

%

100

0

O

-

L

K

GPM

Display range is

Over Limit. Upper

value is

19,990,000 and

transmitter output

is over 100%.

%

100

0

FLOW

GPM

K

99 90

Normal display

for transmitter in

DE mode and

square root

output. Digital

readout is

gallons per

minute with

1000 multiplier.

%

100

0

10 0

.

0

%

OUTPUT MODE

Transmitter is in

output mode.

Bargraph and

readout show

value that was

entered through

SCT or SFC.

%

100

0

7 7

.

9

%

CHECK STATUS

Transmitter in

DE mode is in

non-critical

status.

Displayed value

may not be valid.

If display is “- - -”

instead of a

value,

transmitter is in

critical status.

%

100

0

20 0

.

0

%

Input pressure

equal to or

greater than

200%. Display

flashes between

200% (or twice

current URV in

EU) and O-L.

Transmitter locks

output at 200%

and will go no

higher regardless

of input.

Continued on next page

80

ST 3000 Release 300 Installation Guide

2/05