Table 5 – Honeywell ST 3000 User Manual

Page 28

Advertising
background image

3.1

Considerations for ST 3000 Transmitter,

Continued

Temperature limits

Table 5 lists the operating temperature limits for the various types of
transmitters with silicone fill fluids. See transmitter specifications for
temperature limits of transmitter with alternative fill fluids.

Table 5

Operating Temperature Limits (Transmitters with Silicone Fill Fluids)

Transmitter Type and Model

Ambient Temperature

Process Interface Temperature

°C

°F

°C

°F

Draft Range

STD110

-40 to 70

-40 to 158

-40 to 70

-40 to 158

Differential Pressure STD125
STD120, STD130, STD170

STD904, STD924,

STD930,

STD974

-40 to 85
-40 to 93

-40 to 85

-40 to 185
-40 to 200

-40 to 185

-40 to 85

-40 to 125

-40 to 125

-40 to 185
-40 to 257

-40 to 257

Gauge Pressure
STG140, STG170, STG180,
STG14L, STG17L, STG18L
STG14T
STG93P
STG944,

STG974

STG90L, STG94L,

STG97L,

STG98L


-40 to 93
-40 to 93
-15 to 65
-40 to 85

-40 to 85


-40 to 200
-40 to 200

5 to 149

-40 to 185

-40 to 185


-40 to 125

-40 to 150 †

-15 to 95 ††

-40 to 125

-40 to 110


-40 to 257

-40 to 302 †

5 to 203 ††

-40 to 257

-40 to 230

Absolute Pressure STA122

-40 to 93

-40 to 200

See Specification Sheet

STA140

-40 to 93

-40 to 200

-40 to 80

-40 to 176

STA922

-40 to 85

-40 to 185

See Specification Sheet

STA940

-40 to 85

-40 to 185

-40 to 80

-40 to 176

Flange Mounted
STF128, STF132, STF924,
STF932
Pseudo-Flanged Head
STF12F, STF13F, STF92F,
STF93F
STF14F
Gauge Pressure Flange Mount
STF14T


-40 to 93


-40 to 93
-40 to 85

-40 to 93


-40 to 200


-40 to 200
-40 to 185

-40 to 200


-40 to 175


-40 to 93
-40 to 85

-40 to 150 †


-40 to 350


-40 to 200
-40 to 185

-40 to 302 †

Remote Diaphragm Seals
STR12D, STR13D, STR14G,
STR17G,

STR14A


See Specification Sheet


See Specification Sheet

STR93D, STR94G

-40 to 85

-40 to 185

See Specification Sheet

† Process temperatures above 125 °C (257 °F) require a reduction in the maximum ambient temperature as follows:
Process Temperature

Ambient Temperature Limit

150 °C (302 °F)

50 °C (122 °F)

140 °C (284 °F)

60 °C (140 °F)

125 °C (257 °F)

85 °C (185 °F)

†† Process temperatures above 65 °C (149 °F) require a 1:1 reduction in maximum ambient temperature.
NOTE: For transmitters with local meter option see Table A-2.
NOTE: Transmitters with other fill fluids (CTFE, Neobee, Etc.) have different Operating Temperature Limits. For
more specific information, refer to the appropriate Specification and Model Selection Guide or transmitter nameplate

18

ST 3000 Release 300 Installation Guide

2/05