Specifications

I/O Module Configuration

Release F

UMC800 Controller Installation and User Guide

95

4/01

Component

Parameter

Description

Inputs per Module

6 (ID 3) or 16 (ID B) dry
contact

Logic Inputs

(Module ID 3 and B)

Switching Voltage

5 Vdc

Switching Current

5 mA

Digital Outputs

AC Outputs

(Module ID 8)

DC Outputs

(Module ID 7)

Outputs per Module

6

6 (current sinking)

Operating Voltage

15 Vac to 240 Vac

10.2 Vdc to 26.4 Vdc

Output Type

SSR (Triac)

NPN open collector

Peak Voltage

264 Vac

40 Vdc

AC Frequency

47 Hz to 63 Hz

N/A

ON Voltage Drop

<1.5 Vac (>0.1A)
<3.0 Vac (<0.1A)

1.5 Vdc maximum

Maximum Load
Current

0.5 A per point or
2 outputs at 2.0 A and
4 outputs at 0.5 A

0.3 A per point

Maximum Leakage
Current

4 mA (240 Vac, 60 Hz)
1.2 mA (100 Vac, 60 Hz)
0.9 mA (100 Vac, 50 Hz)

0.1 mA @ 40 Vdc

Maximum Inrush
Current

10 A for 10 ms

1 A for 10 ms

Minimum Load

10 mA

0.5 mA

Base Power required *

20 mA / ON pt. 250 mA
maximum

100 mA maximum
5 V

OFF to ON Response

1 ms

1 ms

ON to OFF response

1 ms +1/2 cycle

1 ms

Fuses
5 x 20mm

1 per output, 1.5 A slow blow

1 per output
1 A fast blow