Replacing the power supply fuse

The power supply input circuit is protected with a fuse. Use the steps in the table below to replace the fuse
on the power supply module.

Step

Action

1

Remove power from the controller.

2

Locate the fuse holder located on the power supply module. See Figure 36.

3

Using a slotted screwdriver, remove the fuseholder cap by rotating it counterclockwise.

4

Replace the fuse with the proper size and type.

For 100-240 V supply: Size 5x20, F 3.15 A Time Delay 250 V, or equivalent.

For 24 V supply: Size 5x20, 6.3 A Slow Blow, or equivalent.

5

Replace the cap by pressing in and rotating it clockwise with the screwdriver.

_

100 - 24 0 V ~

50 / 60 Hz

100 VA MAX.

F 3,15 A T

250V

L1

L2 / N

CPU Battery
Location

Fuse Holder

POWER

LoBAT

FORCE

RUN

DIS

PL

A

Y

BAT

CO

M

M

B

CO

M

M

A

R

e

pl

ac

e ba

tt

e

ry

w

it

h

Ta

di

ra

n

T

L

51

01

/S

on

ly

.

U

s

e

o

f

a

n

o

th

er

ba

tte

ry

m

a

y

pr

e

s

e

nt

a

ris

k

o

f

fi

re

o

r e

x

pl

osi

on

.

S

e

e us

e

rs

g

ui

de

f

o

r i

ns

tr

uct

io

n

s

.

Power
Supply

CPU
Module

Figure 36 Power supply fuse and CPU battery location