Design – Honeywell UMC800 User Manual

Page 105

Advertising
background image

Specifications

Design

Release F

UMC800 Controller Installation and User Guide

97

4/01

Design

Parameter

Description

Scan Rate

1 AI module – (1 to 4 analog inputs): 333 milliseconds
2 AI modules – (5 to 8 analog inputs): 500 milliseconds
3 AI modules – (9 to 12 analog inputs): 700 milliseconds
4 AI modules – (13 to 16 analog inputs): 900 milliseconds
5 AI modules – (17 to 20 analog inputs): 1100 milliseconds
6 AI modules – (21 to 24 analog inputs): 1300 milliseconds
7 AI modules – (25 to 28 analog inputs): 1500 milliseconds
8 AI modules – (29 to 32 analog inputs): 1700 milliseconds
9 AI modules – (33 to 36 analog inputs): 1900 milliseconds
10 AI modules – (37 to 40 analog inputs): 2100 milliseconds
11 AI modules – (41 to 44 analog inputs): 2300 milliseconds
12 AI modules – (45 to 48 analog inputs): 2500 milliseconds
13 AI modules – (49 to 52 analog inputs): 2700 milliseconds
14 AI modules – (53 to 56 analog inputs): 2900 milliseconds
15 AI modules – (57 to 60 analog inputs): 3100 milliseconds
16 AI modules – (61 to 64 analog inputs): 3300 milliseconds

Scan rate dependent upon the number and type of configured function blocks.

Analog outputs will be updated at the same rate as analog inputs.

Fast Logic digital I/O will be serviced one time every 100 msec.

Setpoint Programmers

Up to four independent setpoint programs can be configured with up to 50 segments
each. Up to 70 programs maximum storage.

Power Supply

Standard: 100 Vac to 240 Vac, 50 Hz or 60 Hz; or 100 Vdc to 240 Vdc
Fuse: 3.15 A T 250v, or equivalent.

Optional: 24 V dc or ac, 50 Hz or 60 Hz
Fuse: 6.3 A slow blow, or equivalent.

Power Consumption

100 VA maximum

CPU Battery

Lithium: Tadiran TL5101/SPD ½ AA, 3.6 Vdc

Wiring

Removable terminal blocks with cross-slotted screw terminals; accepts 16 AWG to
22 AWG.

Communications

Two ports for external connections –

CONFIGURATION: RS232 port dedicated connection of the controller to a PC running
the Control Builder Configuration software.

DISPLAY: RS422 port dedicated connection to the Operator Interface.

Optional: Two RS 485 Serial Communication ports, Modbus

®

RTU Protocol, Ethernet

protocol.
Connection: Twisted pair with shield.
Distance: 600 meters, (2000 feet)
Communication mode: Half duplex
Number of devices/link: COMM A: 31, COMM B: 16
Baud Rates: 9600, 19200, 38400

Advertising