Mounting and Wiring

Wiring Communication Links

Release F

UMC800 Controller Installation and User Guide

37

4/01

Table 10 Summary of communication link connections to controller

Communication

Link to . . .

Link Type

From Controller

Port

Connect

Cable

To Port

Reference Data

PC or laptop (via
Null Modem cable
or via modem)

RS 232

CONFIGURATION

(9-pin “D”
connector)

Up to 50 ft
cable lengths
(Supplied by
user)

Serial port of PC.

Null Modem
cable, 9-pin
Male/Female
See Table 11.

Modem: See
Remote Access
(page 44)

Operator interface

RS 422

DISPLAY

(15-pin “D”
connector)

10 ft or 50 ft
cable lengths
available.

Terminal connector
of operator
interface.

See Table 12.

Modbus Link
(optional
communications
board)

RS 485
(Half
Duplex)

COMM A

(4-wire + shield or
2-wire shielded
with external
jumpers

Up to 2000 ft
cable lengths
(Supplied by
user)

Modbus
communications
and PC host.

See Figure 26.

Modbus Link
(optional
communications
board)

RS 485

(Half
Duplex)

COMM B

(4-wire + shield or
2-wire shielded
with external
jumpers

Up to 2000 ft
cable lengths
(Supplied by
user)

Modbus
communications
and slave devices.-

See Figure 26.

CONFIGURATION connector

The Configuration connector accommodates a 9-pin D-type Null Modem cable connection to the serial
RS-232 input of a PC or laptop computer. Table 11 describes the pinouts for the connector. See Figure 23
for the pin numbering. If you need to construct the cable, Table 12 shows the make up of the cable.

Table 11 Configuration connector pinouts

Configuration Connector Pinouts

(For Null Modem Cable)

Signal Name

Terminal No.

DCD

1

RXD

2

TXD

3

DTR

4

GND

5

DSR

6

RTS

7

CTS

8

RI

9