Diagnostics and Troubleshooting
Fault Detection and Troubleclearing

84

UMC800 Controller Installation and User Guide

Release F

4/01

Controller

Diagnostic Summary

(In the User Utility and Operator

Interface)

Controller

LED on CPU

Fault Detection / Troubleclearing

Menu

Item

Status

Possible Cause

Controller Action

User Action

CPU

SPURIOUS
INTERRUPT

POWER
LED flashes
4 times.

Spurious Interrupt.

Executes normally.

1.

Force a cold
start. (Toggle
controller mode
switch from
PGM to RUN.)

2.

Isolate system
from noise and
force a cold
start.

3.

Replace CPU
board.

MEMORY

GOOD

none

MEMORY

LOW BATTERY

Lo BATT
LED on.

Battery voltage is
low.

Executes normally.

Replace battery.

MEMORY

FLASH ERROR

POWER
LED flashes
5 times.

Flash PROM failed
to burn.

Executes normally.

1.

Force a cold
start. (Toggle
controller mode
switch from
PGM to RUN.)

2.

If fault
reappears,
replace CPU
board.

GOOD

none

RTC
(Real
Time
Clock)

NOT
PROGRAMMED

POWER
LED flashes
6 times.

RTC not
programmed

Time and date is
set to 00:00:00,
January 1, 1970.

Enter correct time
and date.

RTC

BAD DATA

POWER
LED flashes
7 times.

Bad time and date.

Time and date is to
00:00:00, January
1, 1970.

1.

Program RTC.

2.

Cycle power.

3.

Replace CPU.

4.

Replace
boards in
backplane.

5.

Replace
backplane.