Diagnostics and Troubleshooting
Fault Detection and Troubleclearing

88

UMC800 Controller Installation and User Guide

Release F

4/01

I/O Module

Diagnostics

(In The User Utility and

Operator Interface)

Controller

LED on CPU

Fault Detection / Troubleclearing

Menu

Item

Status

Possible Cause

Controller Action

User Action

MODULE
1 through
MODULE
16

BAD MODULE

POWER
LED flashes
11 times.

Analog input or
analog output
board does not
have factory
coefficients, or the
I/O board is not a
supported type.

1.

If the error is an
analog input
board with no
factory
coefficients,
default
coefficients will
be used for the
cold-junction
calculations.

2.

If the error is an
analog output
board with no
factory
coefficients,
default
coefficients will
be used for the
outputs.

3.

If the board is an
unsupported
type, these block
types do the
following:

AI – sets its
output to failsafe

DI – sets its
output to OFF

Replace module.