Bles 4-3 – National Instruments AT E Series User Manual

Page 55

Advertising
background image

Chapter 4

Connecting Signals

AT E Series User Manual

4-8

ni.com

GPCTR0_OUT

DGND

Output

Counter 0 Output—This output is from the general-purpose
counter 0 output.

FREQ_OUT

DGND

Output

Frequency Output—This output is from the frequency
generator output.

Table 4-3. I/O Signal Summary for the AT-MIO-16E-1, AT-MIO-16E-2, and AT-MIO-64E-3

Signal Name

Drive

Impedance

Input/

Output

Protection

(Volts)

On/Off

Source

(mA at V)

Sink

(mA at V)

Rise

Time

(ns)

Bias

ACH<0..63>

AI

100 G

in parallel

with

100 pF

25/15

±200 pA

AISENSE, AISENSE2

AI

100 G

in parallel

with

100 pF

25/15

±200 pA

AIGND

AO

DAC0OUT

AO

0.1

Short-circuit

to ground

5 at 10

5 at –10

20

V/µs

DAC1OUT

AO

0.1

Short-circuit

to ground

5 at 10

5 at –10

20

V/µs

EXTREF

AI

10 k

25/15

AOGND

AO

DGND

DO

VCC

DO

0.1

Short-circuit

to ground

1 A

DIO<0..7>

DIO

Vcc +0.5

13 at

(Vcc –0.4)

24 at 0.4

1.1

50 k

Ω pu

1

SCANCLK

DO

3.5 at

(Vcc –0.4)

5 at 0.4

1.5

50 k

Ω pu

EXTSTROBE*

DO

3.5 at

(Vcc –0.4)

5 at 0.4

1.5

50 k

Ω pu

PFI0/TRIG1

ADIO

10 k

Vcc +0.5/±35

3.5 at

(Vcc –0.4)

5 at 0.4

1.5

50 k

Ω pu

2

Table 4-2. I/O Signal Summary for the AT E Series (Continued)

Signal Name

Reference

Direction

Description

Advertising