§ 4.2§Lock§Connection

4.2.1§Lock§Type

The door station can connect two kinds of lock:

The power-on to unlock type: The lock stays locked when there is no power, and unlocks once it
gets the power from the power supply.

The power-off to unlock type: The lock stays locked when there is power feeding it , and unlocks
once the power is cut off.

4.2.2§Connection§Diagram

The lock can get power from the door station directly or from the additional power supply, we call
these two internal power supply and external power supply separately.

4.2.2.1§Door§Lock§Controlled§with§Internal§Power

LOCK

PS5

1

2

3

6

5

4

7

8

9

#

0

*

RF CARD

CN1

CN2

CN-LK

J/KMB

JP-LK

Bus

EB+ EB-

N.O

LK+

LK-

+12V

1

2

3

T/R- T/R+

IP-MR18

AC

+

-

+ -

To C5-IPC or Distributor

LOCK

Exit Button

Set to 2-3

Connect N.O

and +12V pins

Note:

1. Electronic lock of Power-on-to-unlock type should be used.

2. Working current of lock must be less than 250mA, and working voltage must be DC12V

3. JP-LK must be set to 2-3 position, N.O. and 12V pins of CN-LK must be connected together.

4. Unlock Output(unlock mode) must be set to 0(By default)