017-241-B0 Rev B

Table S — Electrical Specifications

Parameter

Value

INPUT

Voltage (nominal), Vac

120 or 230

Frequency, Hz, ±5%

60/50 (auto-detection), Output frequency = Input frequency

Current, Amps 

(@ nominal Vin and max 

battery charging current)

FXM 350-24: 5.3 / 2.7 @120/230 Vac

FXM 350-48: 5.7 / 2.9 @120/230 Vac

AC Input Circuit Breaker 

Ratings, Amps 

FXM 350-24: 7 / 3.5 @120/230 Vac

FXM 350-48: 7 / 3.5 @120/230 Vac

Battery Circuit Breaker 

Ratings, Amps

FXM 350-48: 15

FXM 350-24: 30

OUTPUT

Voltage (nominal), Vac

120 or 230 and 24 Vac

Frequency, Hz, ±5%

60/50 (output frequency = input frequency)

Power, W/VA

350 Total

24 Vac: 260 VA (max)

120 Vac: 350 VA (max)

Waveform

Pure sine wave

Load Crest Factor

3:1 (load dependent)

Output Voltage Distortion

< 3% THD (resistive load)

Efficiency 

5

Normal Mode

Backup (Inverter) Mode

> 96%

> 82% (48 Vbatt), >75% (24 Vbatt)

Transfer Time, mS 

AVR to Backup
Backup to AVR

5 (typical)

5 (typical)

Line Qualification Time, 

Seconds

3 (factory default), user adjustable to 3, 10, 20, 30, 40, or 50

Battery String Voltage

FXM 350 - 24: 24 VDC

FXM 350 - 48: 48 VDC

Battery Charger Current,

FXM 350 – 24: 6A default user adjustable (0~6A)

FXM 350 – 48: 4A default user adjustable (0~4A)

Battery Charger Temperature 

Compensation

6

-5 mV/°C/Cell (factory default), user adjustable to -2.5, -4, -5 or -6 mV/°C/Cell

Battery type

Anderson Power mating part PP45 or equivalent

1. Capable of operating at 73% of rated full load for up to 2 hours at 74°C. For FXM350, above 55°C ambient, derate output power by 1.4%

per °C rise, up to 74°C max. For Micro350 derate above 50°C

2. Capable of operating at 100% of rated full load below 0°C down to -40°C after the Alpha FXM350 and Micro350 has been stabilized at

0°C for at least 1 hour. Batteries may need battery heater mat at lower temperatures.

3. Derate 2°C per 300 m (1000 ft) above 1400 m (4500 ft).

4. The LCD display may not function below -15°C. It gradually resumes normal operation as the temperature rises above -15°C. This will not

affect the operation of the Alpha FXM.

5. Efficiency is measured at an ambient temperature of 25°C, full resistive condition and nominal Line and Battery voltage.